WC flush actuation
for concealed cistern 2L, combination with WC flush plates Visign for Public 2, Visign for Style 11, 12, and Visign for More 100, 102, 103 flush actuation via on-site potential-free contact
Year built (from): | 1.5.2012 |
Trade mark rights exist for this document, further information can be found at viega.com/legal .
The information in this instruction manual is directed at the following groups of people:
Heating and sanitary professionals and trained personnel
Trained electricians
Operators
Consumers
It is not permitted for individuals without the abovementioned training or qualification to mount, install and, if required, maintain this product. This restriction does not extend to possible operating instructions.
The installation of Viega products must take place in accordance with the general rules of engineering and the Viega instructions for use.
Warning and advisory texts are set aside from the remainder of the text and are labelled with the relevant pictographs.
This symbol warns against possible life-threatening injury.
This symbol warns against possible serious injury.
This symbol warns against possible injury.
This symbol warns against possible damage to property.
Notes give you additional helpful tips.
This instruction for use contains important information about the choice of product or system, assembly and commissioning as well as intended use and, if required, maintenance measures. The information about the products, their properties and application technology are based on the current standards in Europe (e. g. EN) and/or in Germany (e. g. DIN/DVGW).
Some passages in the text may refer to technical codes in Europe/Germany. These should serve as recommendations in the absence of corresponding national regulations. The relevant national laws, standards, regulations, directives and other technical provisions take priority over the German/European directives specified in this manual: The information herein is not binding for other countries and regions; as said above, they should be understood as a recommendation.
The following standards and regulations apply to Germany / Europe. National regulations can be found on the relevant web site of your country at viega.com/standards .
Scope / Notice | Regulations applicable in Germany |
---|---|
suitable masonry walls | EN 1996‑1‑1 |
Protection area for installation of the power pack in shower and bath rooms | VDE 0100‑701 |
Scope / Notice | Regulations applicable in Germany |
---|---|
Electrical approvals | EN 60950 |
Electrical approvals | EN 60335 |
Electrical approvals | EN 61558 |
Danger due to electrical current
An electric shock can lead to burns and serious injury and even death.
Work on the electrics may only be carried out by trained electricians.
WCs in barrier-free sanitary rooms should be equipped with flush actuators that can be easily reached by users and carers. For this purpose, the flush plate of the WC can be combined with a radio-controlled or cabled sensor using an electronic flush actuation. A sensor such as this can be fitted on e. g. the handles of the WC or in any position in the room.
An electrical connection must be planned for the electronic actuation in the area of the cistern when planning.
Flushes can be actuated at certain times via the Hygiene+ function to prevent stagnation in the drinking water lines.
Installation is only possible in the following Viega concealed cisterns:
Cistern model 2H
Cistern model 2L
Ascertain which model is installed before mounting. The following information will help you to determine the model of the cistern installed:
Cistern 2H
The revision shaft of this cistern is found at a height of approx. 1 metre on the front.
Cistern 2L
The revision shaft of this cistern is either found at a height of approx. 75 cm on the front or on the top.
Mounting of the electronic flush actuation is only possible with the following WC flush plates:
Product range | Name within the product range | Model number |
---|---|---|
Visign for Public | 2 | 8327.1 |
Visign for Style | 11, 12 | 8331.1, 8332.1, 8332.4 |
Visign for More | 100, 102, 103, 104 | 8352.1, 8353.1, 8355.1, 8354.1 |
The product has the following technical data:
The flush volumes for the manual flush actuation are:
Small flush volume: 3–4 litres
Large flush volume: 6–9 litres
The following flush volumes can be set for the electronic actuation:
Large flush volume: 4.5 / 6 / 9 litres
Small flush volume: 3 / 4 litres
If the external sensor (e. g. a remote button on the handle) offers two activation options, the electronic actuation can be used to select between the large or small flush volume.
Input (power pack) Netzteiltechnische Daten Technische DatenNetzteil |
---|
Output (power pack) |
100–240 V AC, 50–60 Hz, 180 mA |
6.5 V DC, 920 mA |
Electrical approvals see section Regulations from section: Technical data .
Intervals |
---|
Hygiene flush volumes |
24 / 72 / 168 hours |
3 / 6 / 9 litres |
A signal is sent to control the flush actuation through an external sensor, e. g. a button or photo sensor.
The control transmits the electronic signal to the drive unit.
The motor opens the drain valve via the Bowden cable.
As long as the drain valve is open, the set flush volume will flow into the WC.
Stagnation can lead to the build up of germs (e. g. legionella) in drinking water pipes. It is important to rinse the pipeline regularly to prevent the build up of bacteria. The Viega Hygiene+ function was developed for this reason.
Flushes can be actuated at certain times with the Hygiene+ function. Interval and flush volume will be set as required and saved by the control. All settings remain saved during a power cut.
The system's range of functions can be expanded through the connection of accessories onto the control.
One requires the following accessories to be able to connect a radio receiver – instead of a cable-connected external sensor – as shown:
Signals to actuate the flush (e. g. on support hinged handles) sent by HEWI radio transmitters can be received by the radio receiver model 8350.35.
One requires the following accessories to be able to connect an additional external sensor as shown:
Multiple sensors can be connected at the same time using the extension cable adapter model 8350.36. This is how e. g. two external, cable-connected buttons can be connected.
Additionally required: 1 connection cable sensitive.
Buttons, switches or photo sensors for actuating the flush can be connected to the control on site via the connection cable sensitive model 8355.90.
One requires the following accessories to be able to connect a radio controlled actuator alongside an external sensor as shown:
Multiple sensors can be connected at the same time using the extension cable adapter model 8350.36. This is how e. g. a button can be combined with a radio controlled actuation.
Signals to actuate the flush (e. g. on support hinged handles) sent by HEWI radio transmitters can be received by the radio receiver model 8350.35.
To create a redundant power supply with an additional battery compartment as shown, you will need the following accessories:
The battery compartment can be connected for a redundant power supply using the adapter model 8355.91. The battery compartment is included in the adapter's scope of delivery.
Flush volume
This criterion relates exclusively to the flush volume for flush cycles actuated electronically. The flush volume for hygiene flushes is set separately.
The following settings are possible:
Small flush volume 3 litres, large flush volume 4.5 litres
Small flush volume 3 litres, large flush volume 6 litres (factory setting)
Small flush volume 4 litres, large flush volume 9 litres
The Hygiene+ interval
The following settings are possible:
Hygiene+ function deactivated (factory setting)
Hygiene flush 24 hours after the last use
Hygiene flush 72 hours after the last use
Hygiene flush 168 hours after the last use
Hygiene+ flush volume
The following settings are possible:
Hygiene+ flush volume 3 litres (factory setting)
Hygiene+ flush volume 6 litres
Hygiene+ flush volume 9 litres
You require a flush plate so that the flush can be actuated directly at the WC. The Viega models that can be used are found at Suitable manual flush plates .
Installation set
The set model 8350.14 contains a hollow wall socket to house the power pack and an empty pipe with the right clip to connect the cistern (2H).
Extension cable
2 metre cable model 8352.690 for the extension of the power supply to a maximum of 4.75 metres in length.
Programming set
This programming set is required to change the flush setting or activate the Hygiene+ function. It contains a connection cable with a programming contact and a magnetic pin. The programming contact is mounted behind the panel and connected to the blue terminal on the control. The programming can then take place using the magnetic pin.
The model may only be used for the models mentioned in Areas of use .
The power pack should be mounted in an easily accessible place to allow subsequent access.
Before beginning to tile, a concealed socket should be installed for the power pack with protective pipe to the cistern (installation set Optional accessories ).
If necessary, the power pack cable can be extended to a length of 4.75 metres (two extension cables Optional accessories ).
An extension of the mains supply by more than 5 metres can lead to a situation in which the power is not sufficient to actuate the flush.
Protected zone
According to the applicable regulations, installation of the power pack in the protected zones 0 and 1 of shower rooms and bathrooms is not permitted, see Regulations from section: Fields of application / Mounting conditions .
We recommend installing the power pack outside of the protected zones 0–2.
If external sensors are to be connected to the control, their connection lines or protective pipes must be laid in the cistern before tiling is begun.
The following material is required for mounting:
a suitable flush plate Suitable manual flush plates
Programming set Optional accessories
if necessary, empty pipe from power pack into the cistern
if necessary, accessories for the extension of the system System expansions
The following tools are required for mounting:
flat screwdriver
spanner (SW 19)
knife (cutter)
Danger due to electrical current
An electric shock can lead to burns and serious injury and even death.
Work on the electrics may only be carried out by trained electricians.
Always de-energise the connection line before work is commenced.
Requirements:
A 230 V mains connection is available on site.
The installation position of the power pack complies with the requirements in acc. with Installation position of the power pack .
The connection pipeline is de-energised.
Remove approx. 1 cm of the insulation on the connection pipeline.
Push the connection pipeline into the clamps.
The following work stages and diagrams differ depending on the cistern being used. The relevant steps are marked accordingly.
Requirements:
The cistern is fitted into the pre-wall.
If external sensors are to be connected, the cables must be laid through to the cistern.
The electrical connection is laid all the way into the cistern.
The pre-wall is tiled.
Cut into shaft cover.
Remove shaft cover.
Score the revision shaft along the edge of the tiles with a knife.
Angle the knife to do this so that the cut is made flush to the surface of the wall.
Cut the corners of the revision shaft vertically through to the wall surface.
Bend out and pull down the sides of the revision shaft.
The edge of the revisions shaft must be flush with the wall surface.
Remove cistern cover.
Remove and keep the threaded bolts from the cistern cover.
Dispose of cistern cover.
Only for assembly of the flush plate in cistern 2H or on the front of cistern 2L.
Press the bow backwards from the mounting of the mechanism.
Only for assembly of the flush plate on the top of cistern 2L.
Press the bow backwards from the mounting of the mechanism.
Turn the mechanism's lock by 90° in an anti-clockwise direction.
The mechanism is unlocked and can be removed.
Remove and keep mechanism.
Only with the cistern 2H.
Remove and keep spacer.
Requirements:
The revision shaft is shortened in such a way that it is flush with the upper edge of the tiles.
Mechanism, bow and spacer are removed.
Close corner valve.
Loosen flexible hose on the filling valve (size 19).
Open the corner valve for a few seconds to rinse the pipe.
Re-close corner valve.
Lead the panel into the cistern at an angle.
Align the right side of the holding panel with the shaft frame of the cistern.
The hook on the right side of the holding panel must be positioned on the projection of the shaft frame.
Align the holding panel horizontally.
The bow on the left side of the holding panel must be firmly positioned between the vertical fins of the back wall.
Push the drive unit onto the holding panel.
The drive unit must be secure in the guiding rail.
If the holding panel for the drive unit is mounted, remove holding panel.
Push the Bowden cable unit onto the drain valve from the left.
The Bowden cable unit must be felt to click into place on the drain valve.
Position the holder on the domes.
Push rubber plugs onto the dome to secure the holder.
Observation of the prescribed connection sequence is required. The power supply must always be connected last, to ensure that all of the connected components function.
Mounting is much easier if the plug is inserted into the control outside of the cistern.
Connect the red plug of the Bowden cable unit motor to the red connection of the control.
Connect the blue connection cable from the sensor to the blue connection of the control.
Also observe section Connecting external sensors .
Connect the black cable of the power supply to the outer right connection of the control.
Settings for the control can also already be made at this point. The programming set is easier to connect if the control is not yet installed in the cistern. Commissioning
Insert the control into the bracket in the cistern.
Fit the cable into the upper part of the cistern and fix with the cable ties supplied. The cable must not obstruct any moving parts in the cistern.
Connect the flexible hose onto the filling valve.
Open corner valve.
Insert spacer.
Push the holder for the battery compartment onto the spacer from the left.
Push the battery compartment through the large opening into the holder.
Push the battery compartment into the smaller opening.
The battery compartment must be clicked into place directly behind the cover in the holder.
Hang the mechanism in the bow of the drain valve.
Insert mechanism.
The mechanism must sit exactly in the recesses of the cistern.
Turn the mechanism's lock by 90° in a clockwise direction.
The mechanism is locked.
As the next step, fitting of the flush plate as per the instruction manual supplied.
Requirements:
The revision shaft is shortened in such a way that it is flush with the upper edge of the tiles.
Mechanism and bow have been removed.
Close corner valve.
Loosen flexible hose on the filling valve (size 19).
Open the corner valve for a few seconds to rinse the pipe.
Re-close corner valve.
If the holding panel is not mounted on the Bowden cable unit, position the holding panel.
Place the drive unit onto the holding panel.
Push the Bowden cable unit onto the drain valve from the left.
The Bowden cable unit must be felt to click into place on the drain valve.
Position holder with recess on the corner valve.
Push holder backwards until it clicks into place on the plug in the back wall.
Observation of the prescribed connection sequence is required. The power supply must always be connected last, to ensure that all of the connected components function.
Mounting is much easier if the plug is inserted into the control outside of the cistern.
Connect the red plug of the Bowden cable unit motor to the red connection of the control.
Connect the blue connection cable from the sensor to the blue connection of the control.
Also observe section Connecting external sensors .
Connect the black cable of the power supply to the outer right connection of the control.
Settings for the control can also already be made at this point. The programming set is easier to connect if the control is not yet installed in the cistern. Commissioning
Insert the control into the bracket in the cistern.
Fit the cable into the upper part of the cistern and fix with the cable ties supplied. The cable must not obstruct any moving parts in the cistern.
Connect the flexible hose onto the filling valve.
Open corner valve.
Place the battery compartment onto the control holder.
If necessary, secure the battery compartment with a cable tie.
How to install the mechanism depends on whether the flush plate is to be fitted to the front or top of the cistern.
Hang the mechanism in the bow of the drain valve.
Insert mechanism.
The mechanism must sit exactly in the recesses of the cistern.
Turn the mechanism's lock by 90° in a clockwise direction.
The mechanism is locked.
Hang the mechanism in the bow of the drain valve.
Insert mechanism.
In doing so, ensure that the tracks on the top and bottom edge of the mechanism are in the indentations in the revision shaft of the cistern.
Turn the mechanism's lock by 90° in a clockwise direction.
The mechanism is locked.
As the next step, fitting of the flush plate as per the instruction manual supplied.
Damage to property due to excess voltage
If you apply voltage to the connection cable for the external button, you will damage the control.
Do not apply any external voltage!
Requirements:
Button with locking function or potential-free contact (closure time at least 350 ms) available
Connection cable model 8355.90 available
Connect the contact to actuate the small flush volume between the green (1) and yellow cable (3).
Connect the contact to actuate the large flush volume between the green (1) and white cable (2).
Isolate the brown cable.
Connect the connection cable to the control.
Programming the control can be carried out for 30 minutes after the supply voltage is applied. The control returns to normal operation after 30 minutes – programming is now blocked. If the settings have to be changed after this time, the control must be disconnected from the power supply for at least 10 seconds.
The programming set required to program the device is not included in the scope of delivery. It can be purchased separately as accessory. Optional accessories
Observe the following features during programming:
Only one value can be set per programming step.
The settings are retained, even if there is an interruption in the power supply.
The programming process can be cancelled without a change of the settings by holding the magnetic key in front of the programming contact until no acoustic signal has sounded for more than two seconds.
Requirements:
The revision shaft is open and the control can be accessed.
The control programming block is not active.
The programming set is available.
Remove the protective cap of the programming connection from the control.
Connect the cable of the programming contact to the control.
Hold the magnetic key over the programming contact.
In the following, signals sound to show which setting is active.
Remove magnetic key to enable setting.
The following values can be set by removing the magnetic key:
Remove magnetic key after | Setting |
---|---|
1st acoustic signal | Flush volume small 3 l and large 4.5 l |
2nd acoustic signal | Flush volume small 3 l and large 6 l (factory setting) |
3rd acoustic signal | Flush volume small 4 l and large 9 l |
A double acoustic signal is sounded as confirmation. The setting has been changed successfully.
Remove the cable of the programming contact.
Place a protective cap onto the contact.
The Hygiene+ function is deactivated when delivered. If you wish to use the Hygiene+ function, you must program the following settings.
The flush volume for the Hygiene+ function can only be selected if the Hygiene+ function has been activated by choosing a flushing interval.
If no flush volume is selected after activating the Hygiene+ function, the flush volume is set automatically to the minimum volume.
Requirements:
The revision shaft is open and the control can be accessed.
The control is not active Programming block .
The programming set is available.
Remove the protective cap of the programming connection from the control.
Connect the cable from the programming contact onto the control.
Hold the magnetic key in front of the programming contact.
In the following, signals sound to show which setting is active.
Remove magnetic key to enable setting.
The following values can be set by removing the magnetic key:
Remove magnetic key after | Setting |
---|---|
8th acoustic signal | Hygiene+ flush volume 3 l (factory setting, if Hygiene+ is active) |
9th acoustic signal | Hygiene+ flush volume 6 l |
10th Acoustic signal | Hygiene+ flush volume 9 l |
A double acoustic signal is sounded as confirmation. The setting has been successfully changed.
Remove the cable of the programming contact.
Place a protective cap onto the contact.
Requirements:
The revision shaft is open and the control can be accessed.
The control programming block is not active Programming block .
The programming set is available.
The Hygiene+ interval is set.
Remove the protective cap of the programming connection from the control.
Connect the cable from the programming contact onto the control.
Hold the magnetic key in front of the programming contact.
In the following, signals sound to show which setting is active.
Remove magnetic key to enable setting.
The following values can be set by removing the magnetic key:
Remove magnetic key after | Setting |
---|---|
4th acoustic signal | Hygiene flush function: OFF (factory setting) |
5th acoustic signal | Hygiene flush performed 24 hours after the last flush |
6th acoustic signal | Hygiene flush 72 hours after the last use |
7th acoustic signal | Hygiene flush 168 hours after the last use |
A double acoustic signal is sounded as confirmation. The setting has been successfully changed.
Remove the cable of the programming contact.
Place a protective cap onto the contact.
Error |
---|
WC does not flush |
WC flush runs through |
manual actuation is not working |
Cause | Remedy |
---|---|
Power supply failure | actuate manual flush |
Cistern is not yet completely full | Wait until the cistern is sufficiently full |
No water in cistern, corner valve is closed | Open corner valve |
Control defect | Replace control |
Plug connection power pack / control not made | Create plug connection Connecting the control |
Plug connection drive unit / control not made | Create plug connection Connecting the control |
Dirty seal in filling valve | Check seal, replace if necessary |
Dirty seal in drain valve | Check seal, replace if necessary |
Plug sequence drive unit / control incorrect | Check plug connection, observe coloured marking Connecting the control |
The mechanism is not connected to the bow | Hang the mechanism in the bow |
The flush actuation requires no care.
When maintaining the flush plate, heed the instructions of the flush plate manual.
Only for use of a battery compartment for redundant power supply.
Requirements:
The flush plate has been removed.
The mechanism has been removed (compare Preparing the installation ).
Free access to the cistern can be gained through the revision shaft.
Remove the battery compartment from the cistern.
Open battery compartment and remove flat battery.
Insert new battery and close battery compartment.
Place the battery compartment onto the control holder.
If necessary, secure the battery compartment with a cable tie.
Replace and lock mechanism.
Mount flush plate according to manual.
Separate the product and packaging materials (e. g. paper, metal, plastic or non-ferrous metals) and dispose of in accordance with valid national legal requirements.